agholding

Medium Voltage(Main Load Break Switch Panel)

Load Break Switch

Electrical Component COUNTRY OF ORIGIN(Korea)

Operation MethodElectrically Powered/Manual 
Existence of FuseYes 
Rated Voltage24kV 
Rated CurrentSwitch 630A/Fuse Cpacity 100A 
Switch Class (IEC Standard)E3, M1 Class 
Poles3 Pole 
Rated Making Current104kAp 
Power Frequency Withstand VoltageBetween Earth50kV/1min
Between Pole60kV/1min
Impulse Withstand VoltageBetween Earth125kV/1.2×50㎲
Between Pole145kV/1.2×50㎲
 Load Current 63A100 times
Impulse Withstand VoltageLoop Current 630A20 times
Cable 31.5A10 times
Charging Current 9.45A10 times
Line Charging Current 1.5A10 times
No-load switching performance 1000 times
Rated Breaking Current 40kArms
Rated Transfer Current 1250Arms
Rated Current for Fuse (Fuse-Mounting Type) Mountable up to 100A 1/10/16/20/25/31.5/40/50/63/80/100
Rated Control Voltage DC 110V, AC110, 220V
Rated Control Current 5A
Manual Operating Cable Length Standard 2.0m (Selection 1.5/1.8m)
Certificate & Approval IEC60265-1, IEC62271-105, IEC60282-1, KSC4615

GENERAL CHARACTERISTICS

  • Standard colour – Pebble Gray(RAL 7032), Light Gray(RAL 7305)
  • Installation – in door/out door
  • Compartmented – yes
  • Type of ventilation – natural
  • Ingress protection of HT and LT compartment – IP54
  • Ingress protection class Transformer compartment – IP23D
  • Applicable standard – IEC6227-202,IEC61130-202